Cadillac® Energy CU-E Meter
The choice for accurate energy measurement
The Cadillac® CU-E BTU Meter is designed to measure the energy consumed in hot water heating and chilled water cooling systems. The meter is a rate and totalizing device, which is capable of calculating and displaying Volume, Energy, and Temperatures.
The Cadillac® CU-E BTU / Energy Meter measures the temperature in the feed and return lines via two RTD transmitters and from this calculates the density and enthalpy of the water. In addition, by also measuring the volume of water flowing in the system via the Cadillac® flow meter, the CU-E will then compute, display, and output the Energy consumed.
The New Industry Standard
Combining Cadillac®’s CU-T ultrasonic flow meter with advanced electronics and the capability for temperature inputs the CU-E BTU / Energy meter is quickly become acknowledged as the industry standard. Customers choose the Cadillac® CU-E BTU / Energy Meter because of proven: accuracy, dependability, consistency, maintenance and rangeability.
QUICK CONTACT
DOWNLOADABLE DOCUMENTS
Product Summary
With rising fuel costs the need for improvements in energy measurement has driven the Cadillac® Energy Measurement Systems to be acknowledged as the new industry standard.
APPLICATIONS AND FEATURES
Cadillac® Energy CU-E Meter – Applications
The Cadillac® Energy CU-E Meter is the meter of choice for energy applications. This meter can be applied effectively for the following purposes:
- Energy consumption data source for energy management system, DCS, district-wide systems.
- Basis for internal cost estimation using campus-wide systems.
- Efficiency measuring and monitoring from central control rooms.
- Direct Energy / BTU measurements at both Boiler and point of use locations.
Cadillac® Energy CU-E Meter – Features
The Cadillac® Energy CU-E Meter is the meter of choice for energy applications. This meter contains the following features:
- Heating Mode: Where Positive ΔT’s only are totalized.
- Cooling Mode: Where Negative ΔT’s only are totalized.
OPERATION PRINCIPLES
Cadillac® Energy CU-E Meter — Operation Principles
The Cadillac® CU-E BTU / Energy Meter measures the temperature in the feed and return lines via two RTD sensors/transmitters and from this calculates the density and enthalpy of the water. In addition, by also measuring the volume of water flowing in the system via the Cadillac® flow meter, the CU-E will then compute, display, and output the Energy consumed.
Power is Calculated:
- P = V x p x (htv-htr)
Where:
- P = Power (watts)
- V = Volumetric flow Rate
- p = Density
- htv = Specific enthalpy at Feed temperature
- htr = Specific enthalpy at Return temperature
DIMENSIONS AND SPECS
Cadillac® CU-E BTU Meter – Dimensions
The Cadillac® CU-E BTU dimensions are outlined below:
Cadillac® CU-E BTU Meter – General Specifications
The Cadillac® CU-E BTU includes the following specifications:
Energy Meter
- Meter shall consist of remote electroincs, one pair of matched clamp-on transducers, and pair of matched temp trans.
- Meter available with analog (4-20 mA), digital (pulse or relay) outputs, and RS485 Modbus RTU Communications.
- Four line 16 character backlit LCD providing instantaneous Energy, totalized Energy, velocity, and operational status.
- Meter programmed via integral keypad.
- Flow range: 0 to + 40.0 ft/s (0 to + 12.0 m/s), bi-directional flow.
- Accuracy: Typically ± 2.0% of reading at rates < 1.65 ft/s (accuracy also dependent on flow profile).
- Repeatability: 0.2% of Reading.
- Temperature Range: Transducers 4° to +250°F (- 40 to 121°C), Transmitter 4° to +130°F (- 20 to 60°C)
- Meter housing: NEMA 4X (IP65), ABS plastic (standard).
INSTALLATION
Cadillac® Energy CU-E Meter – Installation
The Cadillac® CU-E BTU / Energy Meter installation instructions are outlinde in the diagram below. By implementing the CU-T Ultrasonic flow metering capability and strap-on temperature sensors/transmitters as part of the CU-E Energy System, the user eliminates the need to bring the system down for installation. With a completely non-intrusive system it allows quick and easy retrofit into an online system. With a 100:1 turn down and +/- 2.0% of the rate accuracy the CU-T flow meter provides a cost effective means to provides a flow measurement, while providing a maintenance free non-mechanical flow technology.With no moving parts or flow line obstruction the CU-T has no mechanical drift, which require re-calibration, and does no cause system head loss creating an unwanted heat source (for chilled water systems), as do all other mechanical and differential pressure flow technologies typically used.The CU-E Energy system provides a quick, easy to install, cost effective way to measure energy consumption with reasonable accuracy for the end user.
CU-E Ultrasonic Chilled/Hot Water Energy System
CU-E Water Energy System
MODEL CODE
Ultrasonic & CU-E Model Mode
Related Articles
Why Condensate Conductivity Is Never Too Low For CMAG Magnetic Flow Meters
Due to the nature of the magnetic flow meter measurement (which uses Faraday’s law to measure voltage/velocity of a liquid as it moves through a magnetic field generated by the coils embedded in the flow tube) there is a requirement for the liquid to maintain a...
Flow Meters And LEED: Your Green Building Certification
In the United States, there are more than 5 million commercial and industrial buildings, and combined they are responsible for 45 percent of the total amount of greenhouse gasses that are generated in this country. Furthermore, the EPA reports that 30 percent of the...